Albi Clad TF Fireproof Specifications

Albi Clad TF Fire Endurance Ratings and Specifications

Typical System Hourly Rating Material Thickness UL Design No.
Beam (Wide Flange)W8 x 31 1 (unrestrained) .090 in. dft N-607
  1.5 (restrained) .090 in. dft N-607
  2.0 (restrained) 140 in. dft N-607
Beam W10 x 88 1.5 (unrestrained) .149 in. dft N-607
  3 (restrained) .400 in. dft UL 11-29-99
Column (Wide Flange)
      W8 x 24
2 .313 in. dft X-625
W10 x 49 1 .055 in. dft X-625
  1.5 .132 in. dft X-625
  2 .310 in. dft X-625
  1.5 .430 in. dft X-625
  3 .550 in. dft X-625
  3.5 .670 in. dft X-625
W12 x 120 1.5 .108 in. dft X-625
  2 .192 in. dft X-625
Column (Hollow Section)
     8-Inch pipe
1 .120 in. dft X-628
(schedule 60) 1.5 .230 in. dft X-628
  2 .370 in. dft X-628
  2.5 .520 in. dft X-628
  3 .660 in. dft X-628
(schedule 100) 3 .625 in. dft X-628
4 x 4 x3/8” 2 .431 in. dft X-628
8 x 8 x3/8” 1 .119 in. dft X-628
8 x 8 x1/2” 2 .334 in. dft X-628
10 x 10 x5/8” 1 .065 in. dft X-628
  2 .265 in. dft X-628
16 x 16 x1/2” 1 .065 in. dft X-628
  2 .334 in. dft X-628
16 x 16 x5/8” 1 .065 in. dft X-628
  2 .265 in. dft X-628