Home Contact Us About Us

Albi Clad TF Fireproof Coating

Albi Clad TF ULI Listings

Albi Clad 800 Fireproof Coating

Albi Clad 800 Specifications

Albi Clad 800 ULI Listings

Albi DriClad Fireproof Coating

Albi DriClad Specifications

Albi DriClad ULI Listings

Typical Installations

  • Hospitals
  • Hotel Atriums
  • Warehouses
  • Parking Garages
  • School Gymnasiums
  • Clean Rooms
  • Convention Center

Albi Clad TF Fire Endurance Ratings and Specifications

Typical System Hourly Rating Material Thickness UL Design No.
Beam (Wide Flange)W8 x 31 1 (unrestrained) .090 in. dft N-607
  1.5 (restrained) .090 in. dft N-607
  2.0 (restrained) 140 in. dft N-607
Beam W10 x 88 1.5 (unrestrained) .149 in. dft N-607
  3 (restrained) .400 in. dft UL 11-29-99
Column (Wide Flange)W8 x 24 2 .313 in. dft X-625
W10 x 49 1 .055 in. dft X-625
  1.5 .132 in. dft X-625
  2 .310 in. dft X-625
  1.5 .430 in. dft X-625
  3 .550 in. dft X-625
  3.5 .670 in. dft X-625
W12 x 120 1.5 .108 in. dft X-625
  2 .192 in. dft X-625
Column (Hollow Section)8-Inch pipe 1 .120 in. dft X-628
(schedule 60) 1.5 .230 in. dft X-628
  2 .370 in. dft X-628
  2.5 .520 in. dft X-628
  3 .660 in. dft X-628
(schedule 100) 3 .625 in. dft X-628
4 x 4 x3/8” 2 .431 in. dft X-628
8 x 8 x3/8” 1 .119 in. dft X-628
8 x 8 x1/2” 2 .334 in. dft X-628
10 x 10 x5/8” 1 .065 in. dft X-628
  2 .265 in. dft X-628
16 x 16 x1/2” 1 .065 in. dft X-628
  2 .334 in. dft X-628
16 x 16 x5/8” 1 .065 in. dft X-628
  2 .265 in. dft X-628